After connecting the DAQ to the motor and completing the installation tutorial, you can perform a preliminary check to ensure everything is properly connected.
Navigate to the DAQs page in the top bar.
Click on the Motor and DAQ combination that needs to be validated.
Turn on the motor and wait at least 1 minute.
Refresh the page and ensure the Last Updated column says Just Now.
Turn off the motor if needed.
Verify the values:
Is the expected current visible on all three lines, with the metrics labeled Current RMS Channel x?
Is the expected voltage visible on all three lines, with the metrics labeled Voltage RMS Channel x?
If any values are significantly off, validate the measurement with a multimeter, check the connections, and repeat the process starting from step 1.